HF-Regulator II para lâmpadas T5 (0-10V)

HF-R 414 TL5 EII 220-240V 50/60Hz

HF-R 414 TL5 EII 220-240V 50/60Hz

  • HF-Regulator II para lâmpadas TL5 – Dimerização: o próximo passo para economizar energia

    Informações sobre o produto

    Transferências

    Folheto
    Size:539.9 kB

    Ver todas as transferências

Vídeos

[trigger to render Video Gallery]

Imagens

Especificações Exibir tudo

General Information
Application Code
EII
Type Version
mk1
Lamp Type
TL5
Number Of Lamps
4 piece/unit
Number Of Products On MCB (16A Type B) (Nom)
28
Automatic Restart
sim
Operating and Electrical
Input Voltage
220-240 V
Input Frequency
50-60 Hz
Operating Frequency (Max)
85 kHz
Operating Frequency (Min)
46 kHz
Ignition Method
Partida programada
Crestfactor (Max)
1.7
Power Factor 100% Load (Nom)
0.98
Ignition Time (Max)
0.2 s
Mains Voltage Performance (AC)
-8%-+6%
Mains Voltage Safety (AC)
-10%-+10%
Earth Leakage Current (Max)
0.5 mA
Inrush Current Width
0.25 ms
Power Losses (Nom)
9.9 W
Inrush Current Peak (Max)
27 A
Wiring
Connector Type Input Terminals
Conector universal WAGO 251  [ Apropriado tanto para ligação automática (ALF e ADS) quanto para ligação manual]
Connector Type Output Terminals
Conector universal WAGO 251  [ Apropriado tanto para ligação automática (ALF e ADS) quanto para ligação manual]
Connector Type Control Input Terminals
Conector universal WAGO 251  [ Apropriado tanto para ligação automática (ALF e ADS) quanto para ligação manual]
Wire Striplength
8.0-9.0 mm
Dual Fixture Master/Slave
-  [ não especificado]
Control Input Terminal Cross Section
0.50-1.00 mm²
Input Terminal Cross Section
0.50-1.00 mm²
Output Terminal Cross Section
0.50-1.00 mm²
Auto Insert (ALF/ADS) Wire Cross Section
0.5 mm²
System characteristics
Rated Ballast-Lamp Power
14 W
Temperature
T-Ambient (Max)
50 °C
T-Ambient (Min)
-20 °C
T-Storage (Max)
80 °C
T-Storage (Min)
-25 °C
Stable Lamp Operation Temperature
Not Specified
T-Ignition (Max)
50 °C
T-Ignition (Min)
0 °C
Controls and Dimming
Control Interface
1-10V
Regulating Level Power
1%-100%
Control Input Protection
Yes (Basic insulation)
Mechanical and Housing
Housing
L 359x39x22
Emergency Operation
Battery Voltage Lamp Ignition
196 V
Battery Voltage Lamp Operation
154-276
Approval and Application
Energy Efficiency Index
A1
EMI 9 kHz ... 30 MHz
EN55015
EMI 30 MHz ... 1000MHz
EN55022 level B
Standard de segurança
IEC 61347-2-3
Standard de desempenho
IEC 60929
Quality Standard
ISO 9000:2000
Environmental Standard
ISO 14001
Harmonic Current Emission Standard
IEC 61000-3-2
Emc Immunity Standard
IEC 61547
Standard de vibração
IEC68-2-6 F c
Bumps Standard
IEC 68-2-29 Eb
Humidity Standard
EN 61347-2-3 clause 11
Temperature Marking
110
Emergency Standard
IEC 60598-2-22
Hum And Noise Level
Inaudível
Product Data
Full product code
871150091364730
Order product name
HF-R 414 TL5 EII 220-240V 50/60Hz
EAN/UPC - Product
8711500913647
Order code
913700614466
Local Code
HF-R 414 TL5EII
Numerator - Quantity Per Pack
1
Numerator - Packs per outer box
10
Material Nr. (12NC)
913700614466
Net Weight (Piece)
0.340 kg
Diagramas de instalação
HF-R 4 lamps TL5/PL-L/TL-D
Diagramas de desempenho

Visualizados recentemente

    • Efetue a gestão dos seus projetos com Os Meus Projetos
      Utilize Os Meus Projetos para criar, guardar, gerir e partilhar artigos e projetos com os seus colegas e membros de equipa.
You are now visiting our Global professional lighting website, visit your local website by going to the USA website