Mais marcas da

    • HF-Regulator II para lâmpadas TL5 – Dimerização: o próximo passo para economizar energia

      HF-R 414 TL5 EII 220-240V 50/60Hz
      HF-R 414 TL5 EII 220-240V 50/60Hz

      HF-R 414 TL5 EII 220-240V 50/60Hz

      N.º material (12NC): 913700614466

      Código completo do produto: 871150091364730

    Especificações Exibir tudo

    General Information
    Application Code
    EII
    Type Version
    mk1
    Lamp Type
    TL5
    Number Of Lamps
    4 peça/unidade
    Number Of Products On MCB (16A Type B) (Nom)
    28
    Automatic Restart
    sim
    Operating and Electrical
    Input Voltage
    220-240 V
    Input Frequency
    50 a 60 Hz
    Operating Frequency (Max)
    85 kHz
    Operating Frequency (Min)
    46 kHz
    Ignition Method
    Partida programada
    Crestfactor (Max)
    1,7
    Power Factor 100% Load (Nom)
    0,98
    Ignition Time (Max)
    0,2 s
    Mains Voltage Performance (AC)
    -8%-+6%
    Mains Voltage Safety (AC)
    -10%-+10%
    Earth Leakage Current (Max)
    0,5 mA
    Inrush Current Width
    0,25 ms
    Power Losses (Nom)
    9.9 W
    Inrush Current Peak (Max)
    27 A
    Wiring
    Connector Type Input Terminals
    Conector universal WAGO 251  [ Apropriado tanto para ligação automática (ALF e ADS) quanto para ligação manual]
    Connector Type Output Terminals
    Conector universal WAGO 251  [ Apropriado tanto para ligação automática (ALF e ADS) quanto para ligação manual]
    Connector Type Control Input Terminals
    Conector universal WAGO 251  [ Apropriado tanto para ligação automática (ALF e ADS) quanto para ligação manual]
    Wire Striplength
    8.0-9.0 mm
    Dual Fixture Master/Slave
    -  [ não especificado]
    Control Input Terminal Cross Section
    0.50-1.00 mm²
    Input Terminal Cross Section
    0.50-1.00 mm²
    Output Terminal Cross Section
    0.50-1.00 mm²
    Auto Insert (ALF/ADS) Wire Cross Section
    0.5 mm²
    System characteristics
    Rated Ballast-Lamp Power
    14 W
    Temperature
    T-Ambient (Max)
    50 °C
    T-Ambient (Min)
    -20 °C
    T-Storage (Max)
    80 °C
    T-Storage (Min)
    -25 °C
    Stable Lamp Operation Temperature
    Not Specified
    T-Ignition (Max)
    50 °C
    T-Ignition (Min)
    0 °C
    Controls and Dimming
    Control Interface
    1-10V
    Regulating Level Power
    1%-100%
    Control Input Protection
    Yes (Basic insulation)
    Mechanical and Housing
    Housing
    L 359x39x22
    Emergency Operation
    Battery Voltage Lamp Ignition
    196 V
    Battery Voltage Lamp Operation
    154-276
    Approval and Application
    Energy Efficiency Index
    A1 BAT
    EMI 9 kHz ... 30 MHz
    EN55015
    EMI 30 MHz ... 1000MHz
    EN55022 level B
    Standard de segurança
    IEC 61347-2-3
    Standard de desempenho
    IEC 60929
    Quality Standard
    ISO 9000:2000
    Environmental Standard
    ISO 14001
    Harmonic Current Emission Standard
    IEC 61000-3-2
    Emc Immunity Standard
    IEC 61547
    Standard de vibração
    IEC68-2-6 F c
    Bumps Standard
    IEC 68-2-29 Eb
    Humidity Standard
    EN 61347-2-3 clause 11
    Approval Marks
    Marca CE
    Certificado ENEC
    Certificado VDE-EMV
    Temperature Marking
    110
    Emergency Standard
    IEC 60598-2-22
    Hum And Noise Level
    Inaudível
    Product Data
    Full product code
    871150091364730
    Order product name
    HF-R 414 TL5 EII 220-240V 50/60Hz
    EAN/UPC - Product
    8711500913647
    Order code
    913700614466
    Local Code
    HF-R 414 TL5EII
    Numerator - Quantity Per Pack
    1
    Numerator - Packs per outer box
    10
    Material Nr. (12NC)
    913700614466
    Net Weight (Piece)
    0,340 kg
    Diagramas de instalação
    Transferências
    Leaflets
    Visuais

    Visualizados recentemente

    • Marque um produto para adicionar
       
    • Marque um produto para adicionar
       
    • Marque um produto para adicionar
       
    Marque um produto para adicionar